New Hackensack Fire District
STANDARD OPERATING GUIDELINES
NK-201 Hose Testing
Printable MS Word Version, Click Here

Purpose:  To establish policy and guidelines relating to testing of fire hose. The procedures are set forth to assure the safety of fire hose use and safety of those personnel conducting the test.

 Responsibility:

·        All members of the New Hackensack Fire Department have the responsibility to learn and follow this guideline.

 Policy: 

 Safety:

 Procedure:

 A)    Equipment Needed:

·        Engine and/or Tanker

·        Hose testing manifold

·        2.5” test gate valve with hole in gate.

·        Clipboard with test sheets

·        Various nozzles or gates to bleed out of hose lines

·        Full PPE

B)     Testing Pressures

  

C)    Testing:

·        Hose on racks and on each piece of apparatus, and any new hose will be tested.

·        An engine and /or a tanker will be placed at end of the test area closest to hydrant. Apparatus will be hooked up to the hydrant.

·        Connect 2.5” test gate valve to the 2.5” discharge.

·        Attach 50-foot section of 3” hose to test valve and connect to manifold. Inspect each coupling for gaskets and tighten each coupling using spanner wrench to ensure tight connections. 

·        Connect lengths of same size hose to the manifold. Do not exceed 300 ft on any line.

·        Make sure all hose lengths have adequate space to lay in a straight run and without kinks or twists.

·        Each length of hose needs to be checked against the master test sheet and sheet needs to be updated with missing or new numbers. New hose lengths will be given a tracking number based on the size of the hose. The Officer in charge of the testing will be responsible for assigning and marking numbers for all new hose.

·        Attach appropriate nozzles, gates, etc., to the end of each line to allow for bleeding of air.

·        Place pump/tanker in gear.

·        Open test gate valve and 2.5” discharge gate. Slowly fill all hose lines.

·        Open the nozzles and relief valves of all lines.

·        Bleed all air out of each line.

·        Close all nozzles and relief valves and check the hose for leakage at the couplings. Tighten all couplings that are leaking. If excessive leakage occurs, the section of hose involved shall be deemed to have failed the test.

·        Slowly raise the pressure to the appropriate pressure as outlined above in section B. continuing to check for leakage. Hose pressure as indicated must be maintained for 5 minutes.  During the testing procedure, the hose shall be inspected for any leaks, bulging, etc.

·        Any hose section that has a burst or leaked during test shall be removed from service. If a section bursts during the five (5) minute test, the test must be stopped and the section replaced. The test shall start over. 

·        At the end of the 5-minute testing period, the pump pressure will be taken down, and the nozzles and relief valves will be slowly opened to bleed off pressure in the lines. Break all hose connections and drain the water from the lines.

·        Any defective hose will be taken out of service, marked, and properly disposed of.

·        All hose testing results will be noted in the Master Inventory records in the RedAlert tracking software.